West-control-solutions MRC 7000 Controller Manual Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement West-control-solutions MRC 7000 Controller Manual. West Control Solutions MRC 7000 Controller Manual User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 74
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Form 2877 • Price $32.00
Edition 7 • © Dec. 1996
Revised February, 1998
MRC 7000
ONE AND TWO PEN CIRCLE CHART RECORDING CONTROLLER
Installation, Wiring, Operation Manual
Brand
Vue de la page 0
1 2 3 4 5 6 ... 73 74

Résumé du contenu

Page 1 - MRC 7000

Form 2877 • Price $32.00Edition 7 • © Dec. 1996Revised February, 1998MRC 7000ONE AND TWO PEN CIRCLE CHART RECORDING CONTROLLERInstallation, Wiring, O

Page 2

103. A separate isolation transformer to feed only instrumentation should be considered. The transformer can isolate the instrument from noise fo

Page 3 - TABLE OF CONTENTS

11FIGURE 2-2FIGURE 2-3Coil0.5mfd1000V220ohms115V 1/4W230V 1WInductiveLoadRCMOV

Page 4 - FLOW CHARTS

122.5.2 SENSOR PLACEMENT (THERMOCOUPLE OR RTD)If the temperature probe is to be subjected to corrosive or abrasive conditions, it should beprotected

Page 5 - Product Description 1.1

13RTD LEAD RESISTANCERTD lead length can affect instrument accuracy. Size (gauge) and length of the wire usedaffects lead length resistance.To determ

Page 6 - 1.1.5 ALARM

14Wiring Connections 2.6All wiring connections are typically made to the instrument at the time of installation. Connec-tions are made at the termina

Page 7 - FIGURE 1-2

1512TB1Connect the ACground at thegreen ground screwon the left side ofthe inside of the caseLine 1Line 2TB4 or TB512345+-Grounded orUngroundedThermoc

Page 8 - Mounting 2.4

16FIGURE 2-8Volt, Millivolt and milliamp InputMake the volt, millivolt and milliamp connections as shown below. Use TB4 for thePen 1 input,and TB5 fo

Page 9 - Preparations for Wiring 2.5

17FIGURE 2-10Digital Communications OptionsConnections are made as shown using TB2. Refer to the Protocol Manual, Form #2878 formore details regardin

Page 10 - 2.5.1.2 AC POWER WIRING

18FIGURE 2-11BSPDT Relay OutputFIGURE 2-12SSR Driver OutputConnections are made to relays H through A as shown. Terminal connections are made usingTB

Page 11 - FIGURE 2-3

19FIGURE 2-14Transmitter Power Supply InputIf the isolated 24 VDC regulated transmitter power supply has been specified, the connectionsshould be mad

Page 12 - THERMOCOUPLE LEAD RESISTANCE

2I nformation in this installation, wiring, and operation manual is subject to change without notice. One manual is provided wit

Page 13 - RTD LEAD RESISTANCE

20Configuration 3.1After completing installation and wiring of the instrument the configuration (set up) proceduresmust be performed to prepare the i

Page 14 - Wiring Connections 2.6

21Shipped Configuration/Jumper Positioning 3.2Each instrument is factory shipped ready to accept a thermocouple input on TB 4 and TB 5.All parameters

Page 15 - FIGURE 2-6

223.4.1 POWER UP PROCEDUREStep 1Verify that all electrical connections have been properly made before applying power to theinstrument.Step 2A - For in

Page 16 - FIGURE 2-9

233.5.2 KEYPAD CONTROLSThe keys on the keypad functions include:SCROLL: Used to : 1. Display the enabled modes.2. While in a mode, used to sequenc

Page 17 - AT 115 VAC

24FIGURE 3-1LAMP TESTFrom the Off or Control modes, all display and status LEDs can be illuminated simultaneouslyby depressing the UP and DOWN keys a

Page 18 - TB6 THRU TB

25PROGRAM MODE FLOW CHARTiCorout1o1uLo1LLout2inPSProgo2uLo2LLAL1AL2diSPdPoSEuuEuLHyCoAABHyAorSPrSPuONOFFActual DisplayOn/Off Display - Use arrow keyst

Page 19 - + - +

26SPuLSPLLAtFrPrnddFFrSPLPFFPoutPouPoLCruCrLP1ECP2ECPAECCCBrLyArLybrLyCDONOFFActual DisplayOn/Off Display - Use arrow keysto turn on or offScroll KeyN

Page 20 - Configuration 3.1

27rLyErLyFrLygrLyHCurArLydCurbCurCCurdCobrCoCrCodrEDCom (Optional)CrtPAPuC00CConCbsCAd1CoArECAd2

Page 21 - Start up Procedures 3.4

28TABLE 3-1 PROGRAM MODE CONFIGURATION PROCEDUREPress the SCROLL key until Prog is displayed. Press the DOWN key to enter the Programmode. Pen 1 will

Page 22 - Front Panel Operation 3.5

294 Output 1 Percent o1uL 0 to 100 percent100Upper Limit(o1uLand o1LL willnot be seen if out1 = 0,1,2)5 Output 1 Percent o1LL 0 to 100 percent0Lower L

Page 23 - 3.5.2 KEYPAD CONTROLS

3TABLE OF CONTENTSSECTION 1 - GENERAL PAGE NUMBER1.1 Product Description 5SECTION 2 - INSTALLATION & WIRING2.1 Installation & Wiring 82.2

Page 24 - FIGURE 3-1

3016 Hysteresis for HyAo 0 to 3003Alarm Outputs Width of Hysteresis Band(see page 66 for definition)17 Remote Setpoint rSP 0 to 20If rSP is set to zer

Page 25 - PROGRAM MODE FLOW CHART

3133 Pen Action on PAEC 0 or 11Error Condition 0 = Pen goes to 0 % of chart1 = Pen goes to 100 % of chartPressing the SCROLL key with the PAEC paramet

Page 26

3247 Current Output B Cobr Same selection as CoAr1Range48 Current Output C CoCr Same selection as CoAr1Range49 Current Output D Codr Same selection as

Page 27

33TUNE MODE FLOW CHARTPAL1dAL1bAL1PAL2dAL2SoPtunEbAL2Pb1Pb2rSEtArStrAtECt1Ct2SEnSAAFoPONOFFActual DisplayOn/Off Display - Use arrow keysto turn on or

Page 28

34TABLE 3-2 TUNE MODE CONFIGURATION PROCEDUREThe Tune mode allows the entry, review or altering of the process control Tune adjustmentsand alarm setti

Page 29

3511 Automatic Reset ArSt 0.0 to 100.0 repeats0.0Integration per minute(Will be seen if Pb1 orPb2 was shown)12 Rate Derivative rAtE 0.0 to 10.0 minu

Page 30

36TABLE 3-3 ENABLE MODE CONFIGURATION PROCEDURETo enter the Enable mode, press the UP and DOWN keys while in CtrL or oFF modes. All thedisplay lamps w

Page 31

37Operation 4.14.1.1 OFF MODEIn the Off mode, the instrument control and alarm function (s) are turned off. ProcessRetransmission signal(s) remain

Page 32

38Dual Pen Instruments: If the instrument is specified and provided with the Remote Setpointcapability for either or both pens and the Remote Setpoin

Page 33 - TUNE MODE FLOW CHART

394.1.2.4 TIME PROPORTIONING CONTROLTime Proportioning Control can be implemented on controllers provided with SPST relay orSSR driver output(s). Tim

Page 34

4FIGURES & TABLESFigure 1-1 Recorder Description 5Figure 1-2 Recorder Display 7Figure 2-1 Installation Panel Dimensions Conduit Opening Locati

Page 35

404.1.2.7 PROPORTIONAL OUTPUT PERCENTAGE DISPLAYWhile in the Control mode, pressing the UP and the SCROLL keys at the same time willcause the display

Page 36 - ENABLE MODE FLOW CHART

41STANDBY MODE FLOW CHARTAlarm Operation 4.2There are two alarms available per pen. The type of alarm is selected in the Program modeas follows:1.

Page 37 - Operation 4.1

42Tune Mode Operation 4.3Proportional output controllers may require the adjustment (tuning) of the PID and otherrelated parameters. This provides

Page 38 - 4.1.2.3 ON-OFF CONTROL

434.3.2 ZIEGLER NICHOLS TUNING METHODThis procedure has been determined empirically to yield ideal 1/4 amptitude decay tuningparameters that are dete

Page 39

44Curve A : unstableCurve B : stableCurve C : continuously cycling, ultimate PB and periodACBPeriod

Page 40

45Service 5.1This section contains information regarding calibration and test procedures that can beperformed in the field as well as items concerning

Page 41 - Alarm Operation 4.2

46Calibration 5.4CAUTION: Do not attempt any calibrations without the proper test equipment that meets orexceeds the specifications listed.Press and

Page 42 - Tune Mode Operation 4.3

47TABLE 5-1 CALIBRATION PROCEDURESCalibrationProcedure DescriptionCAL 1 Reinitialization of program and tuning values.CAL 2 Main calibration necessary

Page 43

48Error recovery:See section 5.6 (page 55) for details. Ensure that the millivolt source is connected correctlyand functioning properly.The calibratio

Page 44

495.4.5 CAL 5 RTD INPUTThis procedure determines and saves calibration values relating to RTD inputs. This calibra-tion must be preceded by CAL 2 to p

Page 45 - Changing Pens 5.3

5The number of keys and LED's will depend upon the configuration of individual unit.Product Description 1.11.1.1 GENERALThe instrument is a mic

Page 46 - Calibration 5.4

505.4.7 CAL 9 PEN CALIBRATIONThis procedure is used to calibrate the pen(s). No special test equipment required.Valid inputs must be connected to TB 4

Page 47 - 5.4.2 CAL 2 MAIN CALIBRATION

51Test Mode 5.5To enter the Test mode, press and release the SCROLL key until tESt appears on thedisplay then press the DOWN key. tSt1 will be dis

Page 48

52TABLE 5-2 TEST PROCEDURES AND DESCRIPTIONTest DescriptionTest 1 Microprocessor internal RAM test. Used to check the processor RAM tomake sure it is

Page 49 - 5.4.5 CAL 5 RTD INPUT

535.5.5 TEST 5 KEYPAD/DISPLAY TESTThis test allows the operator to verify that the keys work and that all display elements can belighted. No special t

Page 50 - 5.4.7 CAL 9 PEN CALIBRATION

54The current output reading should be ± 0.1 mADC at any output value. A ± 5 % of spanadjustment for the current output(s) is provided by using the

Page 51 - Test Mode 5.5

55Trouble-shooting and Diagnostics 5.6The Trouble-shooting Guidelines Section consists of two columns. The first column is a list ofsome possible inst

Page 52

56Model Number Displayed 1. Turn off the instrument power, wait 5 seconds thenduring power up is re-apply the power. Verify that the number disp

Page 53

575. If the output appears not to turn off remove the power to the instrument. Open the cover and loosen the platen hold down screw. Swing th

Page 54 - (COMMUNICATIONS OPTIONAL)

584. For software revision R2.99 and below, perform Test 9 as described in the Test Section of the manual (page 54). If the pen feedback volt

Page 55 - CONDITION CORRECTION STEPS

593. If this error appears, check the Program mode parameter dPos, if not 0, change to 0 and see if the error clears.Er 1 - Microprocessor RA

Page 56

61.1.2 RECORDINGThe instrument records the selected process variable on a 10-inch circular chart. One box ofstandard charts is provided with each rec

Page 57

60Er 9 - ADC Reference 1. Perform the CAL2 procedure as described in theNumber Error Calibration section (page 47).Er10 - ADC Reference 1. Perf

Page 58 - ERROR CODE DISPLAYED

61Er36 - Incorrect Crystal 1. Turn off the power to the instrument, wait 5 seconds,For Digital Comm. then turn the power on.Er37 - Incorrect Mic

Page 59

62Appendix ABoard LayoutsFIGURE A-1 - PROCESSOR BOARDUNLOCKEDJU4JU5230TB3TB4 TB5JU364KJU4 PEN 1 INPUT T/C,mV, RTDVOLT/mAJU5 PEN 2 INPUT T/C,mV, RTDVO

Page 60

63If the relay is connected to ahigh impedance AC device,the snubber network used toprotect the relay contact maycause the output to appearto be activ

Page 61

64If the relay is connected to ahigh impedance AC device,the snubber network used toprotect the relay contact maycause the output to appearto be activ

Page 62 - Board Layouts

65If this option board was ordered, you will find it located in the lower right hand corner of theinstrument.FIGURE A-4 - CURRENT OUTPUT BOARDTB10 TB1

Page 63 - TB6 TB7 TB8

66Appendix BGlossaryAutomatic Reset (Integral)This parameter is used so that the instrument will compensate for process variable deviationsfrom setpoi

Page 64

67Pen Action on Power UpThis parameter specifies whether the pen, on a power-up will drive to the "Home Position"(center of chart), then ret

Page 65 - TB10 TB11

68*Total quantity of SPST Relays and SSR Drivers must be less than or equal to (8) eight.**This option comes with a structural foam cover.† N3 - NEMA3

Page 66 - Glossary

69Appendix D Product SpecificationsMeasurement Error Limit • Type J,K,T,E,N,C T/C’s and RTD +/-0.25% of reading plus 1 degree @ 25 degrees C• Type

Page 67

71.1.7 DIGITAL COMMUNICATIONSThe instrument can be ordered with a Digital Communications option that provides thecapability of bi-directional commu

Page 68 - Appendix C Order Matrix

70Input SpecificationsTHERMOCOUPLETYPE RANGE TYPE RANGEJ 0 to 760C E 0 to 750C0 to 1400F 0 to 1400FK 0 to 1360C B 200 to 1800C0 to 2500F 400 to 3300FT

Page 69

71ALARM ADJUSTMENTSProcess Alarm -9999 to 9999 unitsDeviation Alarm -3000 to 3000 unitsDeviation Band Alarm 1 to 3000 unitsHysteresis 0 to 300 unitsCO

Page 70 - Input Specifications

72Appendix ESoftware Reference/Record SheetinPSiCorout1o1uLo1LLout2o2uLo2LLAL1AL2diSPdPoSEuuEuLHyCoHyAorSPrSPurSPLSPuLSPLLAtFrPrnddFFPFFPoutPouPoLCruC

Page 71 - DIGITAL COMMUNICATIONS

73Warranty and Return StatementThese products are sold by The Partlow-West Company under the warranties set forth in thefollowing paragraphs. Such wa

Page 72 - Appendix E

74THE PARTLOW-WEST COMPANY2 CAMPION ROAD • NEW HARTFORD, NY 13413 USA1-800-866-6659 • 315-797-2222 • FAX 315-797-0403

Page 73 - Warranty and Return Statement

8Installation and Wiring 2.1Read these instructions carefully before proceeding with installation and operation. Electricalcode requirements and safe

Page 74 - THE PARTLOW-WEST COMPANY

9FIGURE 2-1Preparations for Wiring 2.52.5.1 WIRING GUIDELINESElectrical noise is a phenomenon typical of industrial environments. The following are

Commentaires sur ces manuels

Pas de commentaire